Customization: | Available |
---|---|
After-sales Service: | User Guides |
Model Number: | Ai208-7-Rb10 |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model
|
Version
|
Panel size
|
Alarm
|
Control output
|
Input type
|
Power supply
|
Code
|
AI208-4/6/7/8-R/SB10
|
Eversion
|
4:48W×48H 6:48W×96H 7:72W×72H 9:96W×96H 80:160W×80H |
1 loop
|
S: SSR R: Relay K: SCR (to be ordered) |
Universal input (TC/RTD)
|
AC/DC 100~240V
|
B0170AI01
|
AI208-9/80-R/SB10
|
B0190AI01
|
||||||
AI208-4/6/7/8-R/SC10
|
B0215AI01
|
||||||
AI208-9/80-R/SC10
|
B0225AI01
|
Sampling speed
|
2 times per second
|
Relay capacity
|
AC 250V /3A Life of rated load>100 thousand times
|
Power supply
|
AC/DC 100 ~ 240V(85-265V)
|
Total consumption
|
< 6VA
|
Ambient environment
|
Indoor use, temperature: 0 ~ 50ºC, no condensation, humidity:<85%RH, altitude<2000m
|
Storage environment
|
-10 ~ 60ºC, no condensation
|
SSR output
|
DC 24V impulse level, load<30mA
|
Insulation impedance
|
Input, output, power to cabinet>20MΩ
|
ESD
|
IEC/EN61000-4-2 Contact ±4KV /Air ±8KV perf.Criteria B
|
Pulse traip anti-interference
|
IEC/EN61000-4-4 ±2KV perf.Criteria B
|
Surge immunity
|
IEC/EN61000-4-5 ±2KV perf.Criteria B
|
Voltage drop & short interruption immunity
|
IEC/EN61000-4-29 0% ~ 70% perf.Criteria B
|
Dielectric strength
|
Signal input & output & power 1500VAC 1min,<60V Low voltage circuit between DC500V, 1min
|
Weight
|
About 400g
|
Shell material
|
PC/ABS (flame class UL94V-0)
|
Panel material
|
PET(F150/F200)
|
Power-off protection
|
10 years, times of writing:1 million times
|
Panel protection class
|
IP65(IEC60529)
|
Safe standard
|
IEC61010-1 Overvoltage category , pollution level 2, (Enhanced insulation) |